Discrete Input Dry Contact IO Card

  • Number of channels: 8 (Series 2), 32 (Series 1)
  • Detection level for On: >2.2 mA
  • Detection level for Off: <1 mA
  • Local Bus Supply: 12 VDC nominal 75 mA typical, 100 mA maximum
  • Field circuit power: 40 mA (8 Channel), 150mA (32 Channel) – maximum at 24VDC 
  • Automatic Redundancy for ‘8 Ch Series 2’ cards